Function Block-Specific Error and Status Codes
Table 85: FB-specific error codes
DiagCode State Name State Description and Output Setting
C001 Reset Error 1 Static Reset signal in state 8001.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
C011 Reset Error 21 Static Reset signal or same signals at EDM1 and Reset (rising trigger at
Reset and EDM1 at the same time) in state C010.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
C021 Reset Error 22 Static Reset signal or same signals at EDM2 and Reset (rising trigger at
Reset and EDM2 at the same time) in state C020.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
C031 Reset Error 23 Static Reset signal or same signals at EDM1, EDM2, and Reset (rising
trigger at Reset, EDM1, and EDM2 at the same time) in state C030.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
C041 Reset Error 31 Static Reset signal or same signals at EDM1 and Reset (rising trigger at
Reset and EDM1 at the same time) in state C040.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
C051 Reset Error 32 Static Reset signal or same signals at EDM2 and Reset (rising trigger at
Reset and EDM2 at the same time) in state C050.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE
C061 Reset Error 33 Static Reset signal or same signals at EDM1, EDM2, and Reset (rising
trigger at Reset, EDM1, and EDM2 at the same time) in state C060.
Ready = TRUE
S_EDM_Out = FALSE
Error = TRUE