DANGER!
The average temperature (MTBF calculation base) for both the extended temperature range (–40 °C
… +70 °C) as well as for standard temperature range (0 °C … +60 °C) is defined to +40 °C.
Ensure that average operating temperature for used AC500-S-XC modules does not exceed +40 °C.
Humidity
Data Value Unit
Relative humidity with condensation (Operating/Storage) 100 %
Air pressure
Data Value Unit
Operating air pressure 1080 … 620 hPa
Operating altitude –1000 … 4000 m
Reduction of operating temperature at an air pressure of < 795
hPa (or > 2000 m above sea level)
10 (e.g. 70 °C to
60 °C)
K
Immunity to corrosive gases
Data Value
Operating: according to: ISA S71.04.1985 Harsh group A, G3/GX IEC 60721-3-3
3C2 / 3C3
yes
Immunity to salt mist
Data Value
Operating: horizontal mounting only, according to: IEC 60068-2-52 severity level:
1
yes
Electromagnectic Compatibility
Data Value
Radiated emission (radio disturbance) according to CISPR 16-2-3 yes
Conducted emission (radio disturbance) according to CISPR 16-2-1, CISPR
16-1-2
yes
Electrostatic discharge (ESD) according to IEC 61000-4-2, zone B, criterion B yes
Fast transient interference voltages (burst) according to IEC 61000-4-4, zone B,
criterion B
yes
High energy transient interference voltages (surge) according to IEC 61000-4-5,
zone B, criterion B
yes
Influence of radiated disturbances according to IEC 61000-4-3, zone B, criterion A yes
Influence of line-conducted interferences according to IEC 61000-4-6, zone B, cri-
terion A
yes
System data for AC500-S-XC
30.03.2017 AC500-S 447