158 Serial communications
ACH550-01 User's Manual
1606 LOCAL LOCK -6…8
Defines control for the use of the HAND mode. The HAND mode allows
drive control from the control panel (operator keypad).
• When
LOCAL LOCK is active, the control panel cannot change from
the AUTO mode to the HAND mode.
8 = COMM – Defines bit 14 of Command Word 1 (parameter 0301) as the
control for setting the local lock.
• The Command Word is supplied through fieldbus communication.
1607 PARAM SAVE 0=DONE, 1=SAVE
Saves all altered parameters to the permanent memory.
• Parameters altered through a fieldbus are not automatically saved to
the permanent memory. To save, you must use this parameter.
• If 1602
PARAMETER LOCK = 2 (NOT SAVED), parameters altered from
the control panel (operator keypad) are not saved. To save, you must
use this parameter.
• If 1602
PARAMETER LOCK = 1 (OPEN), parameters altered from the
control panel are stored immediately to permanent memory.
0 = DONE – The value changes automatically when all parameters are
saved.
1 =
SAVE… – Saves altered parameters to the permanent memory.
1608 START ENABLE 1 -6…7
Selects the source of the Start enable 1 signal. See the figure on page
214.
Note: Start enable functionality differs from the Run enable
functionality.
7 =
COMM – Assigns the fieldbus Command Word as the source for the
Start enable 1 signal.
• Bit 2 of Command Word 2 (parameter 0302) activates the Start
disable 1 signal.
• See the fieldbus user’s manual for detailed instructions.
1609 START ENABLE 2 -6…7
Selects the source of the Start enable 2 signal.
Note: Start enable functionality differs from the Run enable
functionality.
7 =
COMM – Assigns the fieldbus Command Word as the source for the
Start enable 2 signal.
• Bit 3 of Command Word 2 (parameter 0302) activates the Start
disable 2 signal.
• See the fieldbus user’s manual for detailed instructions.