174 Parameter listing and descriptions
ACH550-01 User's Manual
0122 RO 1-3 STATUS 0…111 (0…7 decimal)
Status of the three relay outputs
1 indicates that the relay is energised.
0 indicates that the relay is de-energised.
0123 RO 4-6 STATUS 0…111 (0…7 decimal)
Status of the three relay outputs. See parameter 0122.
0124 AO 1 0…20 mA
Analogue output 1 value in milliamperes
0125 AO 2 0…20 mA
Analogue output 2 value in milliamperes
0126 PID 1 OUTPUT -1000…1000%
Process PID (PID1) controller output value in %
0127 PID 2 OUTPUT -100…100%
External PID (PID2) controller output value in %
0128 PID 1 SETPNT unit and scale defined
by par. 4006/4106 and
PID1 controller setpoint signal 4007/4107
Units and scale defined by PID parameters
0129 PID 2 SETPNT unit and scale defined
by par. 4206 and 4207
PID2 controller setpoint signal
Units and scale defined by PID parameters
0130 PID 1 FBK unit and scale defined
by par. 4006/4106 and
PID1 controller feedback signal 4007/4107
Units and scale defined by PID parameters
0131 PID 2 FBK unit and scale defined
par. 4206 and 4207
PID2 controller feedback signal
Units and scale defined by PID parameters
0132 PID 1 DEVIATION unit and scale defined
by par. 4006/4106 and
Difference between the PID1 controller 4007/4107
reference value and actual value
Units and scale defined by PID parameters
Code Description Range
RELAY 1 STATUS
RELAY
2 STATUS
RELAY
3 STATUS