322 Parameter listing and descriptions
ACH550-01 User's Manual
5 = DI5 – Enables the Interlock function, and assigns a digital input
(starting with
DI5) to the interlock signal for each PFA relay. These
assignments are defined in the following table and depend on:
the number of PFA relays [number of parameters 1401…1403 and
1410…1412 with value = 31 (PFA)]
the Autochange function status (disabled if 8118
AUTOCHNG INTERV =
0.0, and otherwise enabled).
6 =
DI6 – Enables the Interlock function, and assigns digital input DI6 to
the interlock signal for the speed regulated motor.
Requires 8118
AUTOCHNG INTERV = 0.0.
Code Description Range
No. PFA
relays
Autochange disabled
(P 8118)
Autochange enabled
(P 8118)
0
DI1…DI4: Free
DI5: Speed Reg Motor
DI6: Free
Not allowed
1
DI1…DI4: Free
DI5: Speed Reg Motor
DI6: First PFA Relay
DI1…DI4: Free
DI5: First PFA Relay
DI6: Free
2 Not allowed
DI1…DI4: Free
DI5: First PFA Relay
DI6: Second PFA Relay
3…6 Not allowed Not allowed
No. PFA
relays
Autochange disabled Autochange enabled
0
DI1…DI5: Free
DI6: Speed Reg Motor
Not allowed
1 Not allowed
DI1…DI5: Free
DI6: First PFA Relay
2…6 Not allowed Not allowed