EasyManua.ls Logo

ABB ACS580MV - Ground Cable and Cable Shield Connections; Grounding of the Drive System

ABB ACS580MV
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical installation 67
Ground cable and cable shield connections
The cabinet is equipped with ground buses (marked PE, Protective Earth) for grounding
the armor and shields of the cables, and for the connection of the ground cable.
To identify the ground buses, see ACS580MV Wiring Diagram.
Grounding of the drive system
Grounding of the drive system must be in line with the ACS580MV Engineering Guideline.
Auxiliary power supply interface
Terminal
Wire cross section (mm
2
)
Solid wire Flexible wire
-S4: 1,3,5 1.5...35 mm
2
-F11: 1,3,5 1.5...25 mm
2
-F31: 1 1.5...25 mm
2
-F4: 1 1.5...25 mm
2
I/O module terminal sizes
Wire cross section (mm
2
)
Solid wire Flexible wire
Digital inputs 0.5...2.5 mm
2
Digital outputs 0.5...2.5 mm
2
Analog inputs 0.5...2.5 mm
2
Analog outputs 0.5...2.5 mm
2

Table of Contents

Other manuals for ABB ACS580MV