78 Electrical installation
Power cable entry from bottom ((1) screen extensions to ground)
Checking the cable insulation
Check the insulation of each cable before connection and verify that the results are
within the specification of the cable manufacturer.
Leave the cables unconnected at both ends until the commissioning personnel has
given permission to connect them.
Connections
Connect the cables to their corresponding busbars:
Feeder cables to busbars U1, V1, W1
Motor cables to busbars U2, V2, W2
Screen ends of all conductors and the shields of all cables to the PE ground busbar
Ground cable to the PE ground busbar
Bolted connections
Material requirements
Use stainless steel bolts and nuts with the appropriate steel grade and property class
for the connection (recommended: A2-70 [designation according to ISO 3506]).