EasyManua.ls Logo

ABB ACS580MV - Installing Auxiliary, Control and Serial Communication Cables; Further Information

ABB ACS580MV
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical installation 79
Nuts with bonded coating can be used as an alternative to uncoated stainless steel
nuts.
Connection type
The following connection type is recommended when connecting a cable lug (4) to a
busbar:
Spring washer (1) and flat washer (2) on each side of the busbar (3).
Other washers can be used, provided they maintain the required contact pressure.
Use cable lugs suitable for M12 bolts. The required tightening torque is 40 Nm.
Lubrication
If stainless steel bolts and nuts are used, lubricate the thread and head contact
surface of the bolt using recommended pasts, e.g. Molykote D paste.
Note: If a coated nut (e.g. with bonded molybdenum-disulfide [MoS
2
] coating) is used,
the connection does not have to be lubricated.
Tightening torque
Tighten bolted connections with bolts of sizes M10 and greater with the recommended
nominal torque for the bolt size used.
Installing auxiliary, control and serial communication
cables
Further information
See ACS580MV Base frame & TEU layout design for information on:
Project-specific cable entry
1
2
3
1
2
4
6
5
1 Spring washer (2 pcs. per terminal)
2 Flat washers (2 pcs. per terminal)
3 Busbar
4 Cable lug
5 M12 bolt
6 M12 nut