Technical data
102
Symbols
Note: The ratings apply in ambient temperature of 40 °C (104 °F). In lower temperatures the ratings are
higher.
Input cable fuses
The recommended fuses are for branch circuit protection per NEC. Check that the
operating time of the fuse is below 0.5 seconds and the fuses are of the “non-
time delay” type . The operating time depends on the fuse type (T/L or aR), supply
network impedance and the cross-sectional area, material and length of the supply
cable. In case the 0.5 seconds operating time is exceeded with T/L fuses, ultrarapid
(aR) fuses will in most cases reduce the operating time to an acceptable level. The
fuses must be of the “non-time delay” type. See also Planning the electrical
installation / Thermal overload and short-circuit protection.
Note 1: In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 2: Larger fuses must not be used.
Note 3: Fuses from other manufacturers can be used if they meet the ratings.
I
max
maximum output current. Available for 10 s ar start, otherwise as long as allowed by drive
temperature.
Normal use (10 % overload capability)
I
2N
continuous rms current. 10 % overload is typically allowed for one minute every 5 minutes.
P
N
typical motor power. The power ratings apply to most 4-pole NEMA rated motors (230 V or
460 V).
Heavy-duty use (50 % overload capability)
I
2hd
continuous rms current. 50 % overload is typically allowed for one minute every 5 minutes.
P
hd
typical motor power. The power ratings apply to most 4-pole NEMA rated motors (230 V or
460 V).
ACS800-U2 type Input
current
Fuse
A A V Manufacturer Type UL class
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0080-2 201 250 600 Bussmann JJS-250 T
-0100-2 239 300 600 Bussmann JJS-300 T
-0120-2 285 400 600 Bussmann JJS-400 T
-0140-2 391 500 600 Bussmann JJS-500 T
-0170-2 428 600 600 Bussmann JJS-600 T
-0210-2 506 600 600 Bussmann JJS-600 T
-0230-2 599 800 600 Bussmann KTU-800
1)
L
-0260-2 677 800 600 Bussmann KTU-800
1)
L
-0300-2 707 800 600 Bussmann KTU-800
2)
L