The ACS800-02/U2
22
Enclosure extension
The extension can be used for accommodating customer equipment; it is also
automatically added whenever required by factory-installed options such as
• switch fuse (always included with the enclosure extension)
• line contactor with Category 0 emergency stop devices (start/stop and emergency
stop switches included)
• thermistor relay(s)
• Pt100 relays
• top cable entry/exit
• additional I/O terminal block.
Type code
The type code contains information on the specifications and configuration of the
drive. The first digits from left express the basic configuration (e.g. ACS800-02-
0170-5). The optional selections are given thereafter, separated by + signs (e.g.
+E202). The main selections are described below. Not all selections are available for
all types. For more information, refer to ACS800 Ordering Information (EN code:
64556568, available on request).
Type code selections for the ACS800-02
Selection Alternatives
Product series ACS800 product series
Type 02 free standing. When no options are selected: 6-pulse diode input bridge, IP 21,
Control Panel CDP312R, no EMC filter, Standard Application Program, no enclosure
extension, cabling from below, boards without coating, one set of manuals.
Size Refer to Technical data: IEC ratings
Voltage range
(nominal rating in bold)
2 208/220/230/240 VAC
3 380/400/415 VAC
5 380/400/415/440/460/480/500 VAC
+ options
Construction C111 enclosure extension (bottom entry/exit, switch fuse with gG fuses)
C127 US enclosure extension (US door interlock disconnect switch fuse, US gland/conduit
plate, all components UL/cUL approved)
Resistor braking D150 brake chopper
Filter E202 EMC/RFI filter for first environment TN (grounded) system, restricted (the A limits)
E210 EMC/RFI filter for second environment TN/IT (grounded/ungrounded) system
E208 common mode filter
E209 light common mode filter
Line options (+C111 or
+C127 required)
F250 line contactor
Q951 emergency stop of category 0
F260 ultrarapid line fuses (aR)
Cabinet options (+C111
+C127 required)
G304 115 VAC auxiliary voltage transformer
Cabling H351 top entry (+C111+H353 required)
H353 top exit (+C111+H351 required)
H358 US/UK gland/conduit plate