Technical data
92
Cable types
The table below gives copper and aluminium cable types for different load currents.
Cable sizing is based on
max. 9 cables laid on a cable ladder side by side, ambient
temperature 30 °C, PVC insulation, surface temperature 70 °C (EN 60204-1 and
IEC 60364-5-2/2001).
For other conditions, size the cables according to local safety
regulations, appropriate input voltage and the load current of the drive.
Copper cables with concentric
copper shield
Aluminium cables with concentric
copper shield
Max. load
current
A
Cable type
mm
2
Max. load
current
A
Cable type
mm
2
62 3x16 61 3x25
79 3x25 75 3x35
98 3x35 91 3x50
119 3x50 117 3x70
153 3x70 143 3x95
186 3x95 165 3x120
215 3x120 191 3x150
249 3x150 218 3x185
284 3x185 257 3x240
335 3x240 274 3 x (3x50)
358 3 x (3x50) 285 2 x (3x95)
371 2 x (3x95) 331 2 x (3x120)
431 2 x (3x120) 351 3 x (3x70)
459 3 x (3x70) 382 2 x (3x150)
498 2 x (3x150) 428 3 x (3x95)
557 3 x (3x95) 437 2 x (3x185)
568 2 x (3x185) 496 3 x (3x120)
646 3 x (3x120) 515 2 x (3x240)
671 2 x (3x240) 573 3 x (3x150)
746 3 x (3x150) 655 3 x (3x185)
852 3 x (3x185) 772 3 x (3x240)
1006 3 x (3x240)
PDM code: 00096931-E