Parameters 147
Set4 par act User parameter set 4 has been loaded using parameter 16.09
User set sel.
1024
16.11 User IO sel lo When parameter 16.09 User set sel is set to IO mode, selects
the user parameter set together with parameter 16.12 User IO
sel hi. The status of the source defined by this parameter and
parameter 16.12 select the user parameter set as follows:
Const Bit pointer setting (see Terms and abbreviations on page 93). -
Pointer
16.12 User IO sel hi See parameter 16.11 User IO sel lo.
Const Bit pointer setting (see Terms and abbreviations on page 93). -
Pointer
16.14 Reset ChgParLog Resets the log of latest parameter changes.
Done Reset not requested (normal operation). 0
Reset Reset log of latest parameter changes. The value reverts
automatically to Done.
1
16.15 Menu set sel Loads a short, long or custom parameter list. By default, short
parameter list is displayed by drive.
No request No change has been requested. 0
Load short Load short parameter list. Only a selective list of parameters
will be displayed.
1
Load long Load long parameter list. All parameters will be displayed. 2
16.16 Menu set active Shows which parameter list is active. See parameter 16.15
Menu set sel.
None No parameter list is active. 0
Short menu Short parameter list is active. 1
Long menu Long parameter list is active. All parameters are displayed. 2
16.17 Power unit Selects the unit of power for parameters such as 01.22 Power
inu out, 01.23 Motor power and 99.10 Mot nom power.
kW Kilowatt. 0
hp Horsepower. 1
19
19 Speed calculation
Speed feedback, speed window, etc. settings.
19.01 Speed scaling Defines the terminal speed value used in acceleration and the
initial speed value used in deceleration (see parameter group
22 Speed ref ramp). Also defines the rpm value that
corresponds to 20000 for fieldbus communication with ABB
Drives communication profile.
0 … 30000 rpm Acceleration/deceleration terminal/initial speed. 1 = 1 rpm
No. Name/Value Description FbEq
Status of source
defined by par.
16.11
Status of source
defined by par.
16.12
User parameter
set selected
FALSE FALSE Set 1
TRUE FALSE Set 2
FALSE TRUE Set 3
TRUE TRUE Set 4