Parameters 217
51.32 FBA comm sw ver Displays the common program revision of the adapter module
in format axyz, where a = major revision number, xy = minor
revision numbers. z = correction letter.
Example: 190A = revision 1.90A.
Common program version of adapter module. 1 = 1
51.33 FBA appl sw ver Displays the application program revision of the adapter
module in format axyz, where: a = major revision number, xy
= minor revision numbers, z = correction letter.
Example: 190A = revision 1.90A.
Application program revision of adapter module. 1 = 1
52
52 FBA data in
Selection of data to be transferred from drive to fieldbus
controller.
52.01 FBA data in1 Parameters 52.0152.12 select data to be transferred from
the drive to the fieldbus controller.
4 Status Word (16 bits) 4
5 Actual value 1 (16 bits) 5
6 Actual value 2 (16 bits) 6
14 Status Word (32 bits) 14
15 Actual value 1 (32 bits) 15
16 Actual value 2 (32 bits) 16
101…9999 Parameter index 1 = 1
……
52.12 FBA data in12 See parameter 52.01 FBA data in1.
53
53 FBA data out
Selection of data to be transferred from fieldbus controller to
drive.
53.01 FBA data out1 Parameters 53.0153.12 select data to be transferred from
the fieldbus controller to the drive.
1 Control Word (16 bits) 1
2 Reference REF1 (16 bits) 2
3 Reference REF2 (16 bits) 3
11 Control Word (32 bits) 11
12 Reference REF1 (32 bits) 12
13 Reference REF2 (32 bits) 13
101…9999 Parameter index 1 = 1
……
53.12 FBA data out12 See parameter 53.01 FBA data out1.
56
56 Panel display
Selection of signals to be displayed on control panel.
56.01 Signal1 param Selects the first signal to be displayed on the optional control
panel. The default signal is 01.03 Output frequency.
00.00 … 255.255 1st signal to be displayed. -
56.02 Signal2 param Selects the second signal to be displayed on the optional
control panel. The default signal is 01.04 Motor current.
00.00 … 255.255 2nd signal to be displayed. -
No. Name/Value Description FbEq