Parameters 95
01.27 Run-time counter Motor run-time counter. The counter runs when the inverter
modulates. Can be reset using the DriveStudio PC tool.
1=1h
01.28 Fan on-time Running time of the drive cooling fan. Can be reset by
entering 0.
1 = 1 h
01.29 Torq nom scale Nominal torque which corresponds to 100%.
Note: This value is copied from parameter 99.12 Mot nom
torque if entered. Otherwise the value is calculated.
1000 =
1N•m
01.30 Polepairs Calculated number of pole pairs in the motor. 1 = 1
01.31 Mech time const Mechanical time constant of the drive and the machinery as
determined by the speed controller autotune function.
See parameter 23.20 PI tune mode on page 165.
1000 = 1 s
01.32 Temp phase A Measured temperature of phase U power stage in percent of
fault limit.
10 = 1%
01.33 Temp phase B Measured temperature of phase V power stage in percent of
fault limit.
10 = 1%
01.34 Temp phase C Measured temperature of phase W power stage in percent
below fault limit.
10 = 1%
01.35 Saved energy Energy saved in kWh compared to direct-on-line motor
connection.
See parameter group 45 Energy optimising on page 211.
1 = 1 kWh
01.36 Saved amount Monetary savings compared to direct-on-line motor
connection. This value is a multiplication of parameters 01.35
Saved energy and 45.02 Energy tariff1.
See parameter group 45 Energy optimising on page 211.
1 = 1
01.37 Saved CO2 Reduction in CO
2
emissions in metric tons compared to
direct-on-line motor connection. This value is calculated by
multiplying saved energy in megawatt-hours by 0.5 metric
tons/MWh.
See parameter group 45 Energy optimising on page 211.
1 = 1 metric
ton
02
02 I/O values
Input and output signals.
02.01 DI status Status of digital inputs DI8…DI1. The 7th digit reflects the
start interlock input (DIIL). Example: 01000001 = DI1 and
DIIL are on, DI2…DI6 and DI8 are off.
-
02.02 RO status Status of relay outputs RO7…RO1. Example: 0000001 =
RO1 is energized, RO2…RO7 are de-energized.
-
02.03 DIO status Status of digital input/outputs DIO10…DIO1. Example:
0000001001 = DIO1 and DIO4 are on, remainder are off.
-
02.04 AI1 Value of analogue input AI1 in V or mA. Input type is selected
with jumper J1 on the JCU Control Unit.
1000 = 1 unit
02.05 AI1 scaled Scaled value of analogue input AI1. See parameters 13.04
AI1 max scale and 13.05 AI1 min scale.
1000 = 1 unit
02.06 AI2 Value of analogue input AI2 in V or mA. Input type is selected
with jumper J2 on the JCU Control Unit.
1000 = 1 unit
02.07 AI2 scaled Scaled value of analogue input AI2. See parameters 13.09
AI2 max scale and 13.10 AI2 min scale.
1000 = 1 unit
02.08 AI3 Value of analogue input AI3 in V or mA. For input type
information, see the extension module manual.
1000 = 1 unit
02.09 AI3 scaled Scaled value of analogue input AI3. See parameters 13.14
AI3 max scale and 13.15 AI3 min scale.
1000 = 1 unit