166 Parameters
24
24 Torque ref
Torque reference selection, limitation and modification
settings.
24.01 Torq ref1 sel Selects the source for torque reference 1.
Zero No torque reference selected. 0
AI1 scaled 02.05 AI1 scaled (see page 95). 1073742341
AI2 scaled 02.07 AI2 scaled (see page 95). 1073742343
FBA ref1 02.26 FBA main ref1 (see page 100). 1073742362
FBA ref2 02.27 FBA main ref2 (see page 100). 1073742363
D2D ref1 02.32 D2D ref1 (see page 101). 1073742368
D2D ref2 02.33 D2D ref2 (see page 101). 1073742369
PID out 04.05 Process PID out (see page 102). 1073742853
Pointer Value pointer setting (see Terms and abbreviations on page
93).
-
24.02 Torq ref add sel Selects the source for the torque reference addition. Because
the reference is added after the torque reference selection,
this parameter can be used in speed and torque control
modes.
Note: For safety reasons, this reference addition is not
applied when stop functions are active.
Zero No torque reference addition selected. 0
AI1 scaled 02.05 AI1 scaled (see page 95). 1073742341
AI2 scaled 02.07 AI2 scaled (see page 95). 1073742343
FBA ref1 02.26 FBA main ref1 (see page 100). 1073742362
FBA ref2 02.27 FBA main ref2 (see page 100). 1073742363
D2D ref1 02.32 D2D ref1 (see page 101). 1073742368
D2D ref2 02.33
D2D ref2 (see page 101). 1073742369
PID out 04.05 Process PID out (see page 102). 1073742853
Pointer Value pointer setting (see Terms and abbreviations on page
93).
-
24.03 Maximum torq ref Defines the maximum torque reference.
0.0 … 1000.0% Maximum torque reference. 10 = 1%
24.04 Minimum torq ref Defines the minimum torque reference.
-1000.0 … 0.0% Minimum torque reference. 10 = 1%
24.05 Load share Scales the torque reference to a required level (torque
reference is multiplied by the selected value).
-8.000 … 8.000 Torque reference scaling. 1000 = 1
24.06 Torq ramp up Defines the torque reference ramp-up time, i.e. the time for
the reference to increase from zero to the nominal motor
torque.
0.000 … 60.000 s Torque reference ramp-up time. 1000 = 1 s
24.07 Torq ramp down Defines the torque reference ramp-down time, i.e. the time for
the reference to decrease from the nominal motor torque to
zero.
0.000 … 60.000 s Torque reference ramp-down time. 1000 = 1 s
No. Name/Value Description FbEq