EasyManua.ls Logo

ABB ACS850-04 - Programmable Analog Inputs

ABB ACS850-04
296 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Program features 71
Settings
Parameter group 27 Process PID (page 170).
The PID control macro can be activated from the control panel main menu by
selecting ASSISTANTS – Firmware assistants – Application Macro – PID control. See
also page 86.
Programmable analog inputs
The drive has two programmable analog inputs. Each of the inputs can be
independently set as a voltage (0/2…10 V or -10…10 V) or current (0/4…20 mA)
input by a jumper on the JCU Control Unit. Each input can be filtered, inverted and
scaled. The number of analog inputs can be increased by using FIO-xx I/O
extensions.
t<t
d
t
d
SLEEP MODE
t
wd
t
wd
Motor Speed
t
d
= Sleep delay (27.24)
t
wd
= Wake-up delay (27.26)
Sleep level
(27.23)
STOP START
Actual value
Actual value
Wake-up level
(27.25)
Time
Time
Time
Wake-up level
(27.25)
Non-inverted (source of 27.16 = 0)
Inverted (source of 27.16 = 1)

Table of Contents

Other manuals for ABB ACS850-04

Related product manuals