220 Parameters
Broadcast The control word and reference 1 are sent by the master to all
followers. If the master has this setting, the parameter has no
effect in the followers.
0
Ref1 MC Grps The drive-to-drive control word and reference 1 are only sent
to the drives in the multicast group specified by parameter
57.13 Next ref1 mc grp. This setting can also used in
intermediate followers to form a multicast chain.
1
57.12 Ref1 mc group Selects the multicast group the drive belongs to. See
parameter 57.11 Ref1 msg type.
0…62 Multicast group. 1 = 1
57.13 Next ref1 mc grp Specifies the next multicast group of drives the multicast
message is relayed to. See parameter 57.11 Ref1 msg type.
This parameter is effective only in the master or intermediate
followers (i.e. followers relaying the message to other
followers).
0 No group selected. 0
1…62 Next multicast group in the chain. 1 = 1
57.14 Nr ref1 mc grps In the master drive, sets the total number of links (followers or
groups of followers) in the multicast message chain. See
parameter 57.11 Ref1 msg type.
Notes:
• This parameter has no effect if the drive is a follower.
• The master counts as a member of the chain if
acknowledgement from the last drive to the master is
desired.
1…62 Number of links in the multicast chain. 1 = 1
57.15 D2D com port Defines the hardware to which the drive-to-drive link is
connected. In special cases (such as harsh operating
conditions), the galvanic isolation provided by the RS-485
interface of the FSCA module may make for more robust
communication than the standard drive-to-drive connection.
on-board Connector X5 on the JCU Control Unit is used. 0
Slot 1 An FSCA module installed in JCU option slot 1 is used. 1
Slot 2 An FSCA module installed in JCU option slot 2 is used. 2
Slot 3 An FSCA module installed in JCU option slot 3 is used. 3
64
64 Load analyzer
Peak value and amplitude logger settings. See also section
Load analyzer on page 64.
64.01 PVL signal Selects the signal to be monitored by the peak value logger.
The signal is filtered using the filtering time specified by
parameter 64.02 PVL filt time.
The peak value is stored, along with other pre-selected
signals at the time, into parameters 64.06…64.11.
Parameter 64.03 Reset loggers resets both the peak value
logger and amplitude logger 2. The latest time the loggers
were reset is stored into parameter 64.13.
Speed rpm 01.01 Motor speed rpm (see page 94). 1073742081
Speed % 01.02 Motor speed % (see page 94). 1073742082
Frequency 01.03 Output frequency (see page 94). 1073742083
Current 01.04 Motor current (see page 94). 1073742084
Current % 01.05 Motor current % (see page 94). 1073742085
No. Name/Value Description FbEq