EasyManua.ls Logo

ABB ACS850-04 - Page 221

ABB ACS850-04
296 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters 221
Torque 01.06 Motor torque (see page 94). 1073742086
Dc-voltage 01.07 Dc-voltage (see page 94). 1073742087
Power inu 01.22 Power inu out (see page 94). 1073742102
Power motor 01.23 Motor power (see page 94). 1073742103
Process act 04.03 Process act (see page 102). 1073742851
Proc PID out 04.05 Process PID out (see page 102). 1073742853
Pointer Value pointer setting (see Terms and abbreviations on page
93).
-
64.02 PVL filt time Peak value logger filtering time. See parameter 64.01 PVL
signal.
0.00 … 120.00 s Peak value logger filtering time. 100 = 1 s
64.03 Reset loggers Selects the signal to reset the peak value logger and
amplitude logger 2. (Amplitude logger 1 cannot be reset.)
Const Bit pointer setting (see Terms and abbreviations on page 93). -
Pointer
64.04 AL signal Selects the signal to be monitored by amplitude logger 2. The
signal is sampled at 200 ms intervals when the drive is
running.
The results are displayed by parameters 64.2464.33. Each
parameter represents an amplitude range, and shows what
portion of the samples fall within that range.
The signal value corresponding to 100% is defined by
parameter 64.05 AL signal base.
Parameter 64.03 Reset loggers resets both the peak value
logger and amplitude logger 2. The latest time the loggers
were reset is stored into parameter 64.13.
Note: Amplitude logger 1 is fixed to monitor motor current
(01.04 Motor current). The results are displayed by
parameters 64.1464.23. 100% of the signal value
corresponds to the nominal output current of the drive (see
the appropriate Hardware Manual).
Speed rpm
01.01 Motor speed rpm (see page 94). 1073742081
Speed % 01.02 Motor speed % (see page 94). 1073742082
Frequency 01.03 Output frequency (see page 94). 1073742083
Current 01.04 Motor current (see page 94). 1073742084
Current % 01.05 Motor current % (see page 94). 1073742085
Torque 01.06 Motor torque (see page 94). 1073742086
Dc-voltage 01.07 Dc-voltage (see page 94). 1073742087
Power inu 01.22 Power inu out (see page 94). 1073742102
Power motor 01.23 Motor power (see page 94). 1073742103
Process act 04.03 Process act (see page 102). 1073742851
Proc PID out 04.05 Process PID out (see page 102). 1073742853
Pointer Value pointer setting (see Terms and abbreviations on page
93).
-
64.05 AL signal base Defines the signal value that corresponds to 100% amplitude.
0.00 … 32768.00 Signal value corresponding to 100%. 100 = 1
No. Name/Value Description FbEq