Parameters 231
97.08 Pm flux user Defines the permanent magnet flux.
Note: This parameter is valid only for permanent magnet
motors.
0.00000 … 2.00000
p.u
Permanent magnet flux in per unit. 100000 =
1p.u.
97.09 Rs user SI Defines the stator resistance R
S
of the motor model.
0.00000 …
100.00000 ohm
Stator resistance. 100000 =
1 ohm
97.10 Rr user SI Defines the rotor resistance R
R
of the motor model.
Note: This parameter is valid only for asynchronous motors.
0.00000 …
100.00000 ohm
Rotor resistance. 100000 =
1 ohm
97.11 Lm user SI Defines the main inductance L
M
of the motor model.
Note: This parameter is valid only for asynchronous motors.
0.00 …100000.00
mH
Main inductance. 100 = 1 mH
97.12 SigL user SI Defines the leakage inductance
σL
S
.
Note: This parameter is valid only for asynchronous motors.
0.00 …100000.00
mH
Leakage inductance. 100 = 1 mH
97.13 Ld user SI Defines the direct axis (synchronous) inductance.
Note: This parameter is valid only for permanent magnet
motors.
0.00 …100000.00
mH
Direct axis inductance. 100 = 1 mH
97.14 Lq user SI Defines the quadrature axis (synchronous) inductance.
Note: This parameter is valid only for permanent magnet
motors.
0.00 …100000.00
mH
Quadrature axis inductance. 100 = 1 mH
97.20 PM angle offset Defines an angle offset between the zero position of the
synchronous motor and the zero position of the position
sensor.
Notes:
• The value is in electrical degrees. The electrical angle
equals the mechanical angle multiplied by the number of
motor pole pairs.
• This parameter is valid only for permanent magnet motors.
0…360° Angle offset. 1 = 1°
99
99 Start-up data
Language selection, motor configuration and ID run settings.
99.01 Language Selects the language of the control panel displays.
Note: Not all languages listed below are necessarily
supported.
English English.
Español Spanish.
Deutsch German.
Italiano Italian.
Suomi Finnish.