14 Start-up
Enter the motor data from the motor nameplate.
Asynchronous motor nameplate example:
Permanent magnet motor nameplate example:
Note: Set the motor data to
exactly the same value as
on the motor nameplate.
For example, if the motor
nominal speed is 1470 rpm
on the nameplate, setting
the value of parameter
99.09 Mot nom speed to
1500 rpm results in wrong
operation of the drive.
At least parameters 99.06…99.10 must be set with DTC
control (99.05 Motor ctrl mode = DTC). Better control
accuracy can be achieved by setting also parameters
99.11…99.12.
• motor nominal current
Allowed range: approximately 1/6 × I
2n
… 2 × I
2n
of the
drive (0…2 × I
2nd
if parameter 99.05 Motor ctrl mode =
Scalar). With multimotor drives, see page 16.
99.06 Mot nom current
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C36312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz kW
r/min A
cos
IA/IN
t
E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors