Startup Assistant & Parameters 12-353AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
CONTROL AND
STATUS WORDS
(Continued)
INTERNAL STATE MACHINE
LSU CW (06.39)
Default: Read Only
Range: 0000h - FFFFh
(Only visible with a BCU control unit) Shows the control word sent
to the supply unit from the INULSU (inverter unit/supply unit) state
machine. This parameter is read-only.
Bit Name
Descriptions
0 ON/OFF
1 = Start charging
0 = Open main contactor (switch power
off)
1 OFF 2 0 = Emergency stop (Off2)
2 OFF 3 0 = Emergency stop (Off3)
3 START
1 = Start modulating
0 = Stop modulating
4-6 Reserved
7 RESET
0 -> 1 = Reset an active fault - A fresh
start command is required after reset
8-11 Reserved
12 USER BIT 0
See parameter 06.40 LSU CW user bit 0
selection
13 USER BIT 1
See parameter 06.41 LSU CW user bit 1
selection
14 USER BIT 2
See parameter 06.42 LSU CW user bit 2
selection
15 USER BIT 3
See parameter 06.43 LSU CW user bit 3
selection
LSU CW USER BIT 0
SELECTION (06.40)
Default: MCW user bit 0 (2)
Range: 0 - 5, Other
False (0)
0
True (1)
1
MCW user bit 0 (2)
Bit 12 of 06.01 Main control word
MCW user bit 1 (3)
Bit 13 of 06.01 Main control word
MCW user bit 2 (4)
Bit 14 of 06.01 Main control word
MCW user bit 3 (5)
Bit 15 of 06.01 Main control word
Other [bit]
Source selection (see Terms and abbreviations)
(Only visible with a BCU control unit)
Selects a binary source whose status is transmitted as bit 12 of 06.39
Internal state machine LSU CW to the supply unit.