Startup Assistant & Parameters 12-193AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
ACTUAL VALUES
(Continued)
ABS OUTPUT POWER %
MOTOR NOM (01.66)
Default: Read Only
Range: 0.00 to 300.00%
Output power. Absolute value of 01.15 Output power % of motor nom
ABS OUTPUT POWER (01.65) Default: Read Only
Range: 0.0 to 1600.0%
Motor torque. Absolute value of 01.10 Motor torque.
ABS MOTOR SHAFT POWER
(01.68)
Default: Read Only
Range: 0.0 to 32767.00 kW or HP
Motor shaft power. Absolute value of 01.17 Motor shaft power.
INPUT
REFERENCES
Values of references received from various sources. All parameters in this group are read-only unless
otherwise noted. These parameters are for Fieldbus only.
FB A REFERENCE 1 (03.05)
“Fieldbus” mode reference
Default: Read Only
Range: -100000.00 to + 100000.00
Reference 1 received through eldbus adapter A.
FB A REFERENCE 2 (03.06) Default: Read Only
Range: -100000.00 to + 100000.00
Reference 2 received through eldbus adapter A.
FB B REFERENCE 1 (03.07) Default: Read Only
Range: -100000.00 to + 100000.00
Reference 2 received through eldbus adapter B.
FB B REFERENCE 2 (03.08) Default: Read Only
Range: -100000.00 to + 100000.00
Reference 2 received through eldbus adapter B.
EFB REFERENCE 1 (03.09) Default: Read Only
Range: -30000.00 to + 30000.00
Reference 1 received through the imbedded eldbus interface. Scaled
reference 1 received through the embedded eldbus interface. The
scaling is dened by 58.26 EFB ref1 type.
EFB REFERENCE 2 (03.10) Default: Read Only
Range: -30000.00 to + 30000.00
Reference 2 received through the imbedded eldbus interface. Scaled
reference 2 received through the embedded eldbus interface. The
scaling is dened by 58.27 EFB ref2 type.
WARNINGS AND
FAULTS
Information on warnings and faults that occurred last. All parameters in this group are read-only unless
otherwise noted.
TRIPPING FAULT (04.01) Default: Read Only
Range: 0000h - FFFFh
Code of the 1st active fault (the fault that caused the current trip).
ACTIVE FAULT 2 (04.02) Default: Read Only
Range: 0000h - FFFFh
Code of the 2nd active fault.
ACTIVE FAULT 3 (04.03) Default: Read Only
Range: 0000h - FFFFh
Code of the 3rd active fault.
ACTIVE FAULT 4 (04.04) Default: Read Only
Range: 0000h - FFFFh
Code of the 4th active fault.