12-18 Startup Assistant & Parameters 3AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
ACTUAL VALUES
(Continued)
AMBIENT TEMPERATURE
(01.31)
Default: Read Only
Range: -32768 to +32767
0
C or
0
F
Measured temperature of incoming cooling air. The unit is selected by
parameter 96.16 Unit selection.
INVERTER GWh
REGENERATING (01.32)
Default: Read Only
Range: 0 to 32767 GWh
Motoring energy in GWh. Amount of energy that has passed through
the drive (towards the supply) in full gigawatt-hours. The minimum
value is zero.
INVERTER MWh
REGENERATING (01.33)
Default: Read Only
Range: 0 to 999 MWh
Motoring energy in MWh. Amount of energy that has passed through
the drive (towards the supply) in full megawatt-hours. Whenever the
counter rolls over, 01.32 Inverter GWh regenerating is incremented.
The minimum value is zero.
INVERTER kWh
REGENERATING (01.34)
Default: Read Only
Range: 0 to 999 kWh
Motoring energy in kWh. Amount of energy that has passed through
the drive (towards the supply) in full megawatt-hours. Whenever the
counter rolls over, 01.33 Inverter MWh regenerating is incremented.
The minimum value is zero.
MOT - REGEN ENERGY GWh
(01.35)
Default: Read Only
Range: -32768 to +32767 GWh
Motoring energy in GWh. Amount of net energy (motoring energy -
regenerating energy) that has passed through the drive in full gigawatt
hours.
MOT - REGEN ENERGY MWh
(01.36)
Default: Read Only
Range: -999 to +999 MWh
Motoring energy in MWh. Amount of net energy (motoring energy
- regenerating energy) that has passed through the drive in full
megawatt hours. Whenever the counter rolls over, 01.35 Mot - regen
energy GWh is incremented or decremented.
MOT - REGEN ENERGY kWh
(01.37)
Default: Read Only
Range: -999 to +999 kWh
Motoring energy in kWh. Amount of net energy (motoring energy -
regenerating energy) that has passed through the drive in full kilowatt
hours. Whenever the counter rolls over, 01.36 Mot - regen energy
MWh is incremented or decremented.
ABS MOTOR SPEED USED
(01.61)
Default: Read Only
Range: 0.000 to 30000.00 RPM
Measured or estimated motor speed. Absolute value of 01.01 Motor
speed used.
ABS MOTOR SPEED %
(01.62)
Default: Read Only
Range: 0.00 to 1000.00%
Measured or estimated motor speed. Absolute value of 01.03 Motor
speed %.
ABS OUTPUT FREQUENCY
(01.63)
Default: Read Only
Range: 0.00 to 500.00 Hz
Estimated output frequency. Absolute value of 01.06 Output
frequency.