Startup Assistant & Parameters 12-173AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
ACTUAL VALUES
(Continued)
MOTOR SHAFT POWER
(01.17)
Default: Read Only
Range: -32768 to + 32767 kW or HP
Estimated mechanical power at motor shaft. The unit is selected by
parameter 96.16 Unit selection. A lter time constant for this signal
can be dened by parameter 46.14 Filter time power out.
INVERTER GWh COUNTER
(01.18)
Default: Read Only
Range: 0 - 65535 GWh
Energy in GWh - Amount of energy that has passed through the drive
(in either direction) in full gigawatt-hours. The minimum value is zero.
INVERTER MWh COUNTER
(01.19)
Default: Read Only
Range: 0 - 999 MWh
Energy in MWh - Amount of energy that has passed through the drive
(in either direction) in full megawatt-hours. Whenever the counter rolls
over, 01.18 Inverter GWh counter is incremented. The minimum value
is zero.
INVERTER kWh COUNTER
(01.20)
Default: Read Only
Range: 0 - 999 kWh
Energy in kWh - Amount of energy that has passed through the drive
(in either direction) in full kilowatt-hours. Whenever the counter rolls
over, 01.19 Inverter MWh counter is incremented. The minimum value
is zero.
Fieldbus Equivalent: 10 = 1kWh
U-PHASE CURRENT (01.21) Default: Read Only
Range: -30000.00 to +30000.00A
Measured U-phase current.
V-PHASE CURRENT (01.22) Default: Read Only
Range: -30000.00 to +30000.00A
Measured V-phase current.
W-PHASE CURRENT (01.23) Default: Read Only
Range: -30000.00 to +30000.00A
Measured W-phase current.
FLUX ACTUAL % (01.24) Default: Read Only
Range: -0 to +200%
Used ux reference in percent of nominal ux of motor.
SPEED CHANGE RATE
(01.29)
Default: Read Only
Range: -15000 to +15000 RPM
Rate of actual speed change. Positive values indicate acceleration,
negative values indicate deceleration.
See also parameters 31.32 Emergency ramp supervision, 31.33
Emergency ramp supervision delay, 31.37 Ramp stop supervision and
31.38 Ramp stop supervision delay.
NOMINAL TORQUE SCALE
(01.30)
Default: Read Only
Range: 0.0000 - lb-ft
Nominal Torque - Torque that corresponds to 100% of nominal motor
torque.
The unit is selected by parameter 96.16 Unit selection.
Note: This value is copied from parameter 99.12 Motor nominal torque
if entered. Otherwise the value is calculated from other motor
data.