EasyManua.ls Logo

ABB ACS880-01-061A-3+N5350 - Default I;O Connections

ABB ACS880-01-061A-3+N5350
247 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Applying Power Quick Install Guide 7-33AXD50000011888
7.7 Default I/O Connections
The default I/O connections of the 2-wire mode of the ACS880+N5350 primary control program are shown below.
Figure 7-2
Reference voltage and analog inputs
Analog outputs
Drive-to-drive link
XR01, XR02, XR03 Relay outputs
Digital interlock
Digital input/outputs
Digital inputs
1
2
1
2
3
4
5
6
7
1
2
3
4
1
2
3
1
2
3
1
2
3
1
2
1
2
3
4
5
1
2
1
2
3
4
5
6
XSTO
+24VI
GND
+VREF
-VREF
AGND
AI1+
AI1-
AI2+
AI2-
A01
AGND
A02
AGND
B
A
BGND
NC
COM
NO
NC
COM
NO
NC
COM
DIIL
+24VD
DICOM
+24VD
DIOGND
DI01
DI02
DI1
DI2
DI3
DI4
DI5
DI6
Safe torque o circuits must be closed for the drive
to start. See Hardware manual of drive.
3 NO
24 VDC , 2 A
10 VDC , R
L
1...10 kohm
-10 VDC , R
L
1...10 kohm
Ground
Speed reference
0(2)...10 V, R
in
> 200 kohm
By default not in use
0(4)...20 mA, R
in
> 200 kohm
Motor speed rpm
0...20 mA, R
L
> 500 ohm
Motor torque %
0...20 mA, R
L
> 500 ohm
Drive-to-drive link
Ready
250 VAC / 30 VDC
2 A
Running
250 VAC / 30 VDC
2 A
Faulted (-1)
250 VAC / 30 VDC
2 A
Digital Interlock, Thermostat, Ramp Stop
+24 VDC 200 mA
Digital input ground
+24 VDC 200 mA
Digital input/output ground
Trickle current enable
De-Ice mode enable
Stop (0) / Start (1)
By default, not in use
Acc/Dec me set 1 (0) / set 2 (1)
Constant speed 2 (1 = On)
Reset Fault
External Event,
Vibraon Switch / External Trip
X12 Safety opons connecon
X13 Control panel connecon
X205 Memory unit connecon
XP0W External power input
XAI
XAO
XD2D
XD24
XDIO
XDI
t
o
Wire sizes: 0.5 … 2.5mm
2
(24…12AWG)
Tightening torques: 0.5 N·m (5lbf·in)
for both stranded and solid wiring.
Total load capacity of these
outputs is 4.8W (200mA / 24V)
minus the power taken by DIO1
and DIO2.
Must be Closed for the drive to
Start.
Must be Closed for the drive to
Start.

Table of Contents

Related product manuals