Operating Modes 9-13AXD50000011888
Chapter 9
Operating Modes
The ACS880+N5350 can be placed in any one of 5 different operating modes. These modes are used to quickly set up the
drive to operate from the drive terminal strip or from a network communications card. Many inputs are still programmable.
NOTE: Stop drive and place drive in “Local” before changing mode. Cycle power or reboot drive after changing mode.
CAUTION: Drive may start unexpectedly on changing mode.
9.1 2-Wire Operating Mode (Default)
Figure 9-1 ACS880+N5350 2-Wire Operating Mode Connection Diagram (76.03 = 1)
Reference voltage and analog inputs
Analog outputs
Drive-to-drive link
XR01, XR02, XR03 Relay outputs
Digital interlock
Digital input/outputs
Digital inputs
1
2
1
2
3
4
5
6
7
1
2
3
4
1
2
3
1
2
3
1
2
3
1
2
1
2
3
4
5
1
2
1
2
3
4
5
6
XSTO
+24VI
GND
+VREF
-VREF
AGND
AI1+
AI1-
AI2+
AI2-
A01
AGND
A02
AGND
B
A
BGND
NC
COM
NO
NC
COM
NO
NC
COM
DIIL
+24VD
DICOM
+24VD
DIOGND
DI01
DI02
DI1
DI2
DI3
DI4
DI5
DI6
Safe torque off circuits must be closed for the drive
to start. See Hardware manual of drive.
3 NO
24 VDC , 2 A
10 VDC , R
L
1...10 kohm
-10 VDC , R
L
1...10 kohm
Ground
Speed reference
0(2)...10 V, R
in
> 200 kohm
By default not in use
0(4)...20 mA, R
in
> 200 kohm
Motor speed rpm
0...20 mA, R
L
> 500 ohm
Motor torque %
0...20 mA, R
L
> 500 ohm
Drive-to-drive link
Ready
250 VAC / 30 VDC
2 A
Running
250 VAC / 30 VDC
2 A
Faulted (-1)
250 VAC / 30 VDC
2 A
Digital Interlock, Thermostat, Ramp Stop
+24 VDC 200 mA
Digital input ground
+24 VDC 200 mA
Digital input/output ground
Trickle current enable
De-Ice mode enable
Stop (0) / Start (1)
By default, not in use
Acc/Dec �me set 1 (0) / set 2 (1)
Constant speed 2 (1 = On)
Reset Fault
External Event, Vibra�on Switch
X12 Safety op�ons connec�on
X13 Control panel connec�on