10-4 Additional Setup 3AXD50000011888
10.4 Advanced Drive Settings
See ACS880 Software Manual, 3AUA0000085967, for information on advanced drive functions such as PID and Fieldbus
control.
10.4.1 Access Levels
Access levels are based on CTDD USER, Fieldbus or Expert Commissioner. Selection for access level is contained in the
96.02 passcode parameter; accessible in the programming window (but not the startup assistant, passcode changes are for
expert users only). Changing modes will automatically set access level.
There is no default setting for 96.02. Setting access level to 13 (Fieldbus) opens all Fieldbus applicable parameters. Expert
Commissioner enables all parameters in the drive by setting 96.02 = 12.
Expert Commissioner is set in PID and Custom modes.
Fieldbus operating mode opens up all parameters in groups 50 to 56 and monitoring parameters 3.05, 3.06, 6.01 and 6.11.
CTDD User Default Access Level
Pass Code (96.02) Default: -
Set to values below for access level
14 CTDD User
13 Fieldbus
12 Expert Commissioner
Parameter 96.03 shows the current access level setting, note ABB default will show active with the addition of the set level
shown below. Value is offset by one from the password entered.
Access Level (96.03) Default: Read Only
Range: -
11 Expert Commissioner
12 Fieldbus
13 CTDD User
NOTE: The drive will reset to CTDD User on a power cycle.