Startup Assistant & Parameters 12-393AXD50000011888
Table 12-4 Level 1 Parameter Block Definitions
Block Title
Parameter (Number)
Selection (Value)
Descriptions
CONTROL AND
STATUS WORDS
(Continued)
USER STATUS WORD 1 BIT 2
SEL (06.62)
Default: Emergency stop failed (2)
Range: 0 - 2, Other
False
0
True 1
Emergency stop failed 2 - Bit 8 of 06.17 Drive status word 2
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 2 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 3
SEL (06.63)
Default: Magnetized (2)
Range: 0 - 2, Other
False
0
True 1
Magnetized 2 - Bit 1 of 06.17 Drive status word 2
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 3 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 4
SEL (06.64)
Default: Run disable (2)
Range: 0 - 2, Other
False
0
True 1
Run disable 2 - Bit 5 of 06.18 Start inhibit status word
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 4 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 5
SEL (06.65)
Default: False (0)
Range: 0, 1, Other
False
0
True 1
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 5 of 06.50 User
status word 1.
USER STATUS WORD 1 BIT 6
SEL (06.66)
Default: False (0)
Range: 0, 1, Other
False
0
True 1
Other [bit] Source selection (see Terms and abbreviations)
Selects a binary source whose status is shown as bit 6 of 06.50 User
status word 1.