13-8 Troubleshooting 3AXD50000011888
Table 13-1 Warning Messages (Alphabetical by Keypad Text)
Warning Fault # Cause What to do
Edge counter 2
(Editable message text)
Programmable warning:
33.45 Edge counter 2
warn message
A889 Warning generated by
edge counter 2.
Check the source of the warning (parameter 33.43 Edge
counter 2 source).
Value counter 1
(Editable message text)
Programmable warning:
33.55 Value counter 1
warn message
A88A Warning generated by
value counter 1.
Check the source of the warning (parameter 33.53 Value
counter 1 source).
Value counter 2
(Editable message text)
Programmable warning:
33.65 Value counter 2
warn message
A88B Warning generated by
value counter 2.
Check the source of the warning (parameter 33.63 Value
counter 2 source).
Device clean A88C Warning generated by an
ontime timer.
Programmable warnings:
33.14 On-time 1
warn message
33.24 On-time 2
warn message
Check the event log for an auxiliary code.
Check the source of the warning corresponding to the
code:
0: 33.13 On-time 1 source
1: 33.23 On-time 2 source
10: 05.04 Fan on-time counter.
DC capacitor A88D
Cabinet fan A88E
Cooling fan A88F
Additional cooling A890
AI supervision
Programmable warning:
12.03 AI supervision
function
A8A0 An analog signal is outside
the limits specied for the
analog input.
Check signal level at the analog input.
Check the wiring connected to the input.
Check the minimum and maximum limits of the input in
parameter group 12 Standard AI.
Signal supervision
(Editable message text)
Programmable warning:
32.06 Supervision 1 action
32.16 Supervision 2 action
32.26 Supervision 3 action
A8B0 Warning generated by
a signal supervision
function.
Check the source of the warning (parameter 32.07, 32.17
or 32.28).
External warning 1
(Editable message text)
Programmable warning:
31.01 External event 1 source
31.02 External event 1 type
A981 Fault in external device 1. Check the external device.
Check setting of parameter 31.01 External event 1
source.
External warning 2
(Editable message text)
Programmable warning:
31.03 External event 2 source
31.04 External event 2 type
A982 Fault in external device 2. Check the external device.
Check setting of parameter 31.03 External event 2
source.
External warning 3
(Editable message text)
Programmable warning:
31.05 External event 3 source
31.06 External event 3 type
A983 Fault in external device 3. Check the external device.
Check setting of parameter 31.05 External event 3
source.
External warning 4
(Editable message text)
Programmable warning:
31.07 External event 4 source
31.08 External event 4 type
A984 Fault in external device 4. Check the external device.
Check setting of parameter 31.07 External event 4
source.
External warning 5
(Editable message text)
Programmable warning:
31.09 External event 5 source
31.10 External event 5 type
A985 Fault in external device 5. Check the external device.
Check setting of parameter 31.09 External event 5
source.
FA2FA DDCS com
loss
Programmable warning:
60.79 INU-LSU com loss ctrl
AF80 DDCS (ber optic)
communication between
converters (for example,
the inverter unit and the
supply unit) is lost.
Check status of other converter (parameters 06.36 and
06.39).
Check settings of parameter group 60 DDCS
communication. Check the corresponding settings in the
control program of the other converter.
Check cable connections. If necessary, replace cables.