Troubleshooting 13-113AXD50000011888
Table 13-2 Fault Messages (Alphabetical by Keypad Text)
Fault Fault # Cause What to do
DC link overvoltage 3210 Excessive intermediate
circuit DC voltage.
Check that overvoltage control is on (parameter 30.30
Overvoltage control).
Check that the supply voltage matches the nominal input
voltage of the drive.
Check the supply line for static or transient overvoltage.
Check brake chopper and resistor (if present).
Check deceleration time.
Use coast-to-stop function (if applicable).
Retrot drive with brake chopper and brake resistor.
Check parameter 90.42 Motor speed lter
time is programmed to 30m seconds.
Check the speed loop tuning parameters in group 25, if
the setting are to dymanic this could cause the drive to
fault.
The drive can trip on this fault if the Autophasing time
and level is not high enough for the application, if the
Autophasing levels are programmed to low the fan will not
come to a full stop before the motor starts and this will
could cause the drive to fault.
DC link
undervoltage
3220 Intermediate circuit DC
voltage is not sufcient
because of a missing
supply phase, blown
fuse or fault in the rectier
bridge.
Check supply cabling, fuses and switchgear.
Standby timeout 3280 Automatic restart failed
(see section Automatic
restart.
Check the condition of the supply (voltage, cabling, fuses,
switchgear).
DC voltage
difference
3291 Difference in DC voltages
between parallel-
connected
inverter modules.
Contact your local ABB representative.
Output phase loss
Programmable fault: 31.19
Motor phase loss
3381 Motor circuit fault due to
missing motor connection
(all three phases are not
connected).
Connect motor cable.
Autophasing 3385 Autophasing routine (see
section Autophasing has
failed.
Try other autophasing modes (see parameter 21.13
Autophasing mode) if possible.
Check that the motor ID run has been successfully
completed.
Clear parameter 98.15 Position offset user.
Check that the encoder is not slipping on the motor shaft.
Check that the motor is not already turning when the
autophasing routine starts.
Check the setting of parameter 99.03 Motor type.
Motor cable
overload
4000 Calculated motor cable
temperature has
exceeded warning limit.
Check the settings of parameters 35.61 and 35.62.
Check the dimensioning of the motor cable in regard to
required load.
IGBT
overtemperature
4210 Estimated drive IGBT
temperature is excessive.
Check ambient conditions.
Check air ow and fan operation.
Check heatsink ns for dust pick-up.
Check motor power against drive power.
Cooling 4290 Drive module temperature
is excessive.
Check ambient temperature. If it exceeds 40°C (104°F),
ensure that load current does not exceed derated load
capacity of drive. See appropriate Hardware Manual.
Check drive module cooling air ow and fan operation.
Check inside of cabinet and heatsink of drive module for
dust pick-up. Clean whenever necessary.
IGBT temperature 42F1 Drive IGBT temperature is
excessive.
Check ambient conditions.
Check air ow and fan operation.
Check heatsink ns for dust pick-up.
Check motor power against drive power.