G-4 Ethernet/IP Setup 3AXD50000011888
5. Program the following information below. The ACS880 CTDD Drive only supports the 16 Bit Transparent assembly
instances displayed below. This example will use 16 Bit transparent Prole Assembly Instances 112 and 162. The
following table will display Input and Output Assembly Instances and PLC I/O Memory size.
Input Assembly Instances Output Assembly Instances PLC Word Settings
61 11 2
62 12 3
161 111 12
162 112 13
Reference FENA-01/-11/-21 EtherNet Adapter Module User’s Manual 3AUA0000093568 section “Communication”
for more information on Input/Output Assembly Instances and reference FEIP-21 Ethernet IP User’s Manual
3AXD50000158621.
6. Enter the following information. The example shown is using the B16 Bit Transparent Prole Assembly Instances
112 and 162. The PLC will transmit and receive 13 words of information.
a. Enter the name that will be given to the Cooling Tower Drive
b. Change Comm Format to Data - INT (16Bits)
c. Enter the IP Address of the Ethernet option card
d. Enter Input and Output Assembly Instances numbers.
e. Enter Input and Output Assembly Instances numbers.
f. Enter conguration instance as 1 and size as 0.
7. Click Finish.