12-8 Startup Assistant & Parameters 3AXD50000011888
Table 12-1 Initial Start-up / Motor Data and ID Run
Direction Test
NOTE: The Autophasing delay occurs everytime the
motor starts, including direction testing.
00:00Back
CTDD 50.0 rpmLocal
Direction test
Spin the motor to check direction
No, skip the test
Yes, test now
Next
Use the key to perform a direction test of the
rotation of the motor. Then press (next).
00:00Back
CTDD 50.0 rpmLocal
Direction test
Spin the motor to check direction
No, skip the test
Yes, test now
Next
The following warning message will appear.
Press START to check direction of the motor.
A screen will appear next asking if the motor is
running in the correct direction.
00:00Back
CTDD 50.0 rpmLocal
Press Start
Warning! Until set-up is done, safeties
are not activate and motor speed is
limited between 1/3 to 2/3 speed.
Press Start now to start the motor,
then check the direction of rotation.
Next
Motor set-up is complete.
To exit and save all data, select (Done).
To exit without saving data, select (cancel).
00:00Cancel
50.0 rpmLocal
Motor set-up complete
Connect I/O according to the User
Manual.
Done
CTDD
NOTE: After initial startup sequencing a new power-up will initiate the standard CTDD startup mode (see Table
12-2).