Startup Assistant & Parameters 12-113AXD50000011888
Table 12-2 Drive Assistant
Drive Limit Settings
The CTDD will automatically set limits according to
motor data entered. For most CTDD applications,
the default values are acceptable. However, values
are adjustable within Limits:
Minimum Speed ≥ 10% Motor Speed
Maximum Speed ≤ Motor Speed
Minimum Torque set to -30% (adjustable)
Maximum Torque set to 110% (adjustable)
50.00 rpm
500.00 rpm
-30.0 %
110.0 %
CT Minimum Speed
Maximum speed
Minimum torque
Maximum torque
Acceleration time 1
00:00 NextBack
CTDD 50.0 rpmLocal
Limits
Use the to highlight the ramp rate to be
adjusted. Press to enter the edit screen once
highlighted or (next) if the default value is
acceptable.
110.0 %
100.000 s
100.000 s
100.000 s
100.000 s
Maximum torque
Acceleration time 1
Deceleration time 1
Acceleration time 2
Deceleration time 2
00:00 NextBack
CTDD 50.0 rpmLocal
Limits
Naming the Drive
The default drive name is CTDD. Use to edit the
drive name or (next) to continue.
CTDDDrive name
00:00 NextBack
CTDD 50.0 rpmLocal
Naming the drive
The name will show at the top of the
panel screen, making it easier to see
which motor this drive controls.
Selecting Operating Mode
Select Operating Mode
Operating modes are sets of default wire and
parameters suitable for most CTDD applications.
The active operating mode is displayed, (2-wire)
default. If this is correct, press (next). To edit
the operating mode press .
Caution: Ensure drive is stopped and in Local before
changing mode. Drive could unexpectedly start
when changing mode.
00:00Back
50.0 rpmLocal
Select Operating Mode
Select mode below.
Operating Mode
Next
2-Wire
CTDD

Table of Contents