EasyManua.ls Logo

ABB ACS880-07XT Series - High Speed Mode Ratings

ABB ACS880-07XT Series
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
136 Technical data
High speed mode
Selection High speed mode of parameter 95.15 Special HW settings improves control
performance at high output frequencies. We recommend it to be selected with output
frequency of 120 Hz and above.
This table gives the drive module ratings for 120 Hz output frequency and the maximum
output frequency for the drive ratings when High speed mode in parameter 95.15 Special
HW settings is enabled: With output frequencies smaller than this recommended
maximum output frequency, the current derating is less than the values given in the table.
Contact ABB for operation above the recommended maximum output frequency or for the
output current derating with output frequencies above 120 Hz and below the maximum
output frequency.
Drive
module
type
ACS880-
07XT-
Deratings with selection High speed mode of parameter 95.15 Special HW settings
120 Hz output frequency Maximum output frequency
Nominal use Light-
duty use
Heavy-
duty use
Nominal use Light-
duty
use
Heavy-
duty use
fI
N
P
N
I
Ld
I
Hd
f
max
I
N
P
N
I
Ld
I
Hd
Hz A kW A A Hz A kW A A
U
N
= 400 V
1010A-3 120 1010 544 997 746 500 760 435 729 541
1190A-3 120 1190 650 1167 878 500 892 460 857 637
1330A-3 120 1330 734 1316 1041 500 955 460 913 718
1610A-3 120 1610 915 1570 1274* 500 1159 653 1104 920*
U
N
= 500 V
1010A-5 120 1010 693 997 720 500 696 435 661 519
1160A-5 120 1160 822 1146 878 500 754 460 721 548
1310A-5 120 1310 916 1297 1041 500 850 580 788 666
1610A-5 120 1610 1153 1570 1274* 500 1012 736 938 754
U
N
= 690 V
0810A-7 120 810 753 791 678* 375 546 471 528 445*
0960A-7 120 960 920 929 837 375 552 460 534 482
1080A-7 120 1080 1025 1051 929 375 626 580 607 552
1320A-7 120 1320 1300 1297 1051* 375 828 736 791 644*
3AXD10000363510
f Output frequency
f
max
Maximum output frequency with High speed mode
U
N
Nominal voltage of the drive
I
N
Continuous rms output current. No overload capability at 40 °C (104 °F)
P
N
Typical motor power in no-overload use.
I
Ld
Continuous rms output current allowing 10% overload for 1 minute every 5 minutes
I
Hd
Continuous rms output current allowing 50% overload for 1 minute every 5 minutes
* Continuous rms output current allowing 30% overload for 1 minute every 5 minutes