64 Guidelines for planning the electrical installation
Typical power cable sizes
The tables below give copper and aluminum cable types with concentric copper shield for
the drive modules with nominal current.
1) The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one
on top of the other, ambient temperature 30 °C (86 °F) PVC insulation, surface temperature 70 °C
(158 °F) (EN 60204-1 and IEC 60364-5-52). For other conditions, dimension the cables according to local
safety regulations, appropriate input voltage and the load current of the drive.
Drive type
ACS880-
07XT-
IEC
1)
input and motor cabling
Cabling per basic module Common cabling for the basic modules
Cu cable type Al cable
type
Cu cable type Al cable
type
mm
2
mm
2
mm
2
mm
2
U
N
= 400 V
1010A-3 3 × (3 × 120) 3 × (3 × 185) 4 × (3 × 185) 5 × (3 × 240)
1190A-3 3 × (3 × 150) 3 × (3 × 240) 4 × (3 × 240) 6 × (3 × 240)
1330A-3 3 × (3 × 185) 4 × (3 × 185) 5 × (3 × 240) 6 × (3 × 240)
1610A-3 3 × (3 × 240) 4 × (3 × 240) 6 × (3 × 240) 7 × (3 × 240)
U
N
= 500 V
1010A-5 3 × (3 × 120) 3 × (3 × 185) 4 × (3 × 185) 5 × (3 × 240)
1160A-5 3 × (3 × 150) 3 × (3 × 240) 4 × (3 × 240) 6 × (3 × 240)
1310A-5 3 × (3 × 185) 4 × (3 × 185) 5 × (3 × 240) 6 × (3 × 240)
1610A-5 3 × (3 × 240) 4 × (3 × 240) 6 × (3 × 240) 7 × (3 × 240)
U
N
= 690 V
0810A-7 3 × (3 × 95) 3 × (3 × 120) 4 × (3 × 150) 4 × (3 × 240)
0960A-7 3 × (3 × 120) 3 × (3 × 185) 4 × (3 × 185) 5 × (3 × 185)
1080A-7 3 × (3 × 150) 3 × (3 × 185) 4 × (3 × 240) 5 × (3 × 240)
1320A-7 3 × (3 × 185) 4 × (3 × 185) 5 × (3 × 240) 6 × (3 × 240)