138 Technical data
Dimensions and weights
See chapter Dimensions.
Free space requirements
Losses, cooling data and noise
The cooling air temperature rises 30 degrees Celsius when it goes through the drive
module if the temperature of the input cooling air is 40 degrees Celsius
Terminal and lead-through data for the power cables
The locations and sizes of lead-throughs are shown by the dimension drawings delivered
with the drive, and the dimension drawing.
Front* Sides* Above**
mm in. mm in. mm in.
150 5.91 0 0 400 15.75
*As required by cooling.
**Measured from the base plate of the cabinet top. Note: 320 mm (12.3 in.) is required for fan replacement of
IP54 cabinets.
Drive unit type Frame size Air flow per module Heat
dissipation per
module
Noise
Basic
drive
module
Drive
unit
m
3
/h ft
3
/min W dB(A) dB(A)
U
N
= 400 V
ACS880-07XT-1010A-3 2×R10 1200 707 6409 72 75
ACS880-07XT-1190A-3 2×R10 1200 707 8122 72 75
ACS880-07XT-1330A-3 2×R11 1420 848 8764 71 75
ACS880-07XT-1610A-3 2×R11 1420 848 10578 71 75
U
N
= 500 V
ACS880-07XT-1010A-5 2×R10 1200 707 6409 72 75
ACS880-07XT-1160A-5 2×R10 1200 707 8122 72 75
ACS880-07XT-1310A-5 2×R11 1420 848 8764 71 75
ACS880-07XT-1610A-5 2×R11 1420 848 10578 71 75
U
N
= 690 V
ACS880-07XT-0810A-7 2×R10 1200 707 6409 72 75
ACS880-07XT-0960A-7 2×R11 1420 848 8764 72 75
ACS880-07XT-1080A-7 2×R11 1420 848 9862 71 75
ACS880-07XT-1320A-7 2×R11 1420 848 10578 71 75
>
320 mm (12.28 in.)
>
400 mm
(15.75 in.)
IP22/42 IP54