EasyManua.ls Logo

ABB ACS880-07XT Series - Wiring the Pt100 Relays (Options +2 L506, +3 L506, +5 L506 and +8 L506)

ABB ACS880-07XT Series
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
82 Electrical installation
Wiring the Pt100 relays (options +2L506, +3L506, +5L506 and +8L506)
External wiring of eight Pt100 sensor modules is shown below. Contact load capacity
250 V AC 10 A. For the actual wiring, see the circuit diagram delivered with the drive.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
X506
T
1 × Pt100
2
1
T
T
T
T
T
T
T
3
1 Internal wiring of the windings overheat
(modules 1…3): overtemperature = contact
open.
2 Internal wiring of the bearings overheat
(module 4 and 5): overtemperature = contact
open.
3 Internal wiring of the windings overheat
(modules 6…8): overtemperature = contact
open.

Table of Contents

Related product manuals