EasyManua.ls Logo

ABB ACS880-07XT Series - External Power Supply for the Control Unit (XPOW); DI6 as a PTC Sensor Input

ABB ACS880-07XT Series
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Control units of the drive 99
Notes:
The wire size accepted by all screw terminals (for both stranded and solid wire) is
0.5…2.5mm
2
(24…12 AWG). The torque is 0.5 N·m (5 lbf·in).
1)
See section Drive-to-drive link (XD2D).
2)
See chapter Safe torque off function.
3)
0 = Acceleration/deceleration ramps defined by parameters 23.12/23.13 in use.
1 = Acceleration/deceleration ramps defined by parameters 23.14/23.15 in use.
4)
Constant speed 1 is defined by parameter 22.26.
5)
See section DIIL input (page 100).
6)
Total load capacity of these outputs is 4.8 W (200 mA at 24 V) minus the power taken by
DIO1 and DIO2.
7)
Determines whether DICOM is separated from DIOGND (ie. common reference for
digital inputs floats; in practice, selects whether the digital inputs are used in current
sinking or sourcing mode). See also Ground isolation diagram.
DICOM=DIOGND ON: DICOM connected to DIOGND. OFF: DICOM and DIOGND
separate.
8)
Current [0(4)…20 mA, R
in
= 100 ohm] or voltage [0(2)…10 V, R
in
> 200 kohm] input
selected by switch AI1. Change of setting requires reboot of control unit.
9)
Current [0(4)…20 mA, R
in
= 100 ohm] or voltage [0(2)…10 V, R
in
> 200 kohm] input
selected by switch AI2. Change of setting requires reboot of control unit.
External power supply for the control unit (XPOW)
The BCU-x2 is powered from a 24 V DC, 2 A supply through terminal block XPOW. A
second supply can be connected to the same terminal block for redundancy.
DI6 as a PTC sensor input
A PTC sensor can be connected to this input for motor temperature measurement as
follows. The sensor can alternatively be connected to FEN-xx encoder interface module.
Do not connect both ends of the cable shield directly to ground. If a capacitor cannot be
used at one end, leave that end of the shield unconnected. See the firmware manual for
parameter settings.
T
3.3 nF
>
630 V AC
PTC
DI6
+24VD

Table of Contents

Related product manuals