146 Technical data
sufficient. If in doubt, the supply transformer with static screening between the primary
and secondary windings can be used.
2. An EMC plan for preventing disturbances is drawn up for the installation. A template is
available from the local ABB representative.
3. The motor and control cables are selected as specified in the hardware manual.
4. The drive is installed according to the instructions given in the hardware manual.
WARNING! A drive of category C4 is not intended to be used on a low-voltage public
network which supplies domestic premises. Radio frequency interference is expected if
the drive is used on such a network.
Low
voltage
Equipment
Low
voltage
Equipment
Equipment
(victim)
Supply transformer
Medium voltage network
Static screen
Point of measurement
Drive
Neighbouring
network