Installation and commissioning flowchart
Task See
Identify the frame size of your drive: A, B, C or D. Technical data: Ratings (page 71)
Plan the installation.
Check the ambient conditions, ratings, required
cooling air flow, input power connection, compatibility
of the motor, motor connection, and other technical
data.
Select the cables.
Planning the cabinet assembly (page 25)
Planning the electrical installation (page 37)
Technical data (page 71)
Option manual (if optional equipment is
included)
Unpack and check the units.
Check that all necessary optional modules and
equipment are present and correct.
Only intact units may be started up.
Mechanical installation: Contents of the
package (page 31)
If the converter has been non-operational for
more than one year, the converter DC link
capacitors need to be reformed. Ask ABB for
more information.
Check the installation site. Mechanical installation: Before installation
(page 33)
Technical data (page 71)
If the drive is about to be connected to an IT
(ungrounded) system, check that the screw(s)
labelled VAR are removed. Also note that using a
mains filter is not allowed in an IT (ungrounded]
system.)
Safety instructions: Installation and
maintenance work (page 6)
Install the drive in a cabinet. Mechanical installation: Installation procedure
(page 34)
Route the cables. Planning the electrical installation: Routing the
cables (page 44)
Check the insulation of the supply cable, the motor
and the motor cable, and the resistor cable (if
present).
Electrical installation: Checking the insulation of
the assembly (page 47)