Mains filters
88
Selection table
The mains filters are protected to IP20. Refer to page 106 for dimensions, wire sizes
and tightening torques.
Installation guidelines
If a mains choke is also installed, the mains filter is connected between the mains
choke and the drive module. See the diagram below.
For optimal operation of the filter, the drive and the filter must be mounted on the
same conductive surface
Ensure the filter does not block the airflow through the drive module
Keep the cable between the drive and the filter as short as possible.
Mains filters for ACSM1-04
Drive type
ACSM1-04xx…
Filter type
-02A5-4
JFI-02
-03A0-4
-04A0-4
-05A0-4
-07A0-4
-09A5-4
JFI-03-012A-4
-016A-4
-024A-4
JFI-05
-031A-4
-040A-4
-046A-4
-060A-4
JFI-07-073A-4
-090A-4
PDM-425726