Electrical installation
49
Power cable connection
Power cable connection diagram
1)
(PE) (PE)
3)
PE
For alternatives, see Planning the electrical
installation: Supply disconnecting device
(page 37).
Optional braking resistor
(see the chapter Resistor
braking [page 91])
L1 L2 L3
UDC+ UDC–
R– R+
2)
U2 V2 W2
U1 V1 W1
3
~
Motor
V1
W1U1
ACSM1-04
CHK-xx mains choke (optional). See the chapter
Mains chokes (page 85).
JFI-xx mains filter (optional). See the chapter
Mains filters (page 87).
Notes:
– If shielded supply (input) cable is used, and the conductivity of the shield is less than 50% of the conduc-
tivity of a phase conductor, use a cable with a ground conductor (1) or a separate PE cable (2).
– For motor cabling, use a separate ground cable (3) if the conductivity of the cable shield is less than 50%
of the conductivity of a phase conductor and the cable has no symmetrical ground conductors. See also
section Selecting the power cables on page 41.
PE
The UDC+/UDC– connectors can be used for
common DC configurations. See page 56.