Technical data
75
Supply cable fuses
Fuses for short circuit protection of the supply cable are listed below. The fuses also
protect the adjoining equipment of the drive in case of a short circuit. Check that the
operating time of the fuse is below 0.5 seconds. The operating time depends on the
supply network impedance and the cross-sectional area and length of the supply
cable. See also chapter Planning the electrical installation.
Note: Fuses with a higher current rating must not be used.
Drive type
ACSM1-04xx
Input
current
(A)
IEC fuse UL fuse
Cross-sectional
area of cable
Rated
current
(A)
Voltage
(V)
Class
Rated
current
(A)
Voltage
(V)
UL
Class
mm
2
AWG
-02A5-4 3.2* 6 500 gG 6 600 T 1.5 4 16…12
-03A0-4 4.7* 6 500 gG 6 600 T 1.5 4 16…12
-04A0-4 5.7* 10 500 gG 10 600 T 1.5 4 16…12
-05A0-4 7.8* 10 500 gG 10 600 T 1.5 4 16…12
-07A0-4 9.8* 16 500 gG 15 600 T 1.5 4 16…12
-09A5-4 12* 16 500 gG 15 600 T 1.5 10 16…8
-012A-4 15* 20 500 gG 20 600 T 1.5 10 16…8
-016A-4 20* 25 500 gG 25 600 T 1.5 10 16…8
-024A-4 20 25 500 gG 25 600 T 6…35 9…2
-031A-4 27 32 500 gG 35 600 T 6…35 9…2
-040A-4 33 40 500 gG 45 600 T 6…35 9…2
-046A-4 39 50 500 gG 50 600 T 6…35 9…2
-060A-4 55 63 500 gG 70 600 T 10…70 6 2/0
-073A-4 65 80 500 gG 80 600 T 10…70 6 2/0
-090A-4 78 100 500 gG 100 600 T 10…70 6 2/0
*Without mains choke