Technical data
74
Dimensions and weights
See also the chapter Dimension drawings.
Note: The wiring to the I/O options requires some 50 mm (2”) of additional depth.
Cooling characteristics, noise levels
Cold plate cooling characteristics (ACSM1-04Cx-xxxx-x only)
The ratings stated at the beginning of this chapter are achieved provided that the
hot-spot temperature of the cold plate is kept below 65 °C (140 °F) and that the drive
is installed according to the instructions in this manual.
A suitable cold plate is, for example, the Rittal DCP 8616.xxx (Direct Cooling
Package) intended for Rittal TS8 enclosures. If the incoming coolant temperature is
below 50 °C (122 °F), and the flow is at least 5 dm
3
/min, the cooling is adequate.
The temperature rise of the coolant due to the drive is approximately 1…2 K
maximum.
The ACSM1-04Cx-xxxx-x has an internal fan to cool the circuit boards. The heat
dissipation into air is approximately 200 W.
Frame
size
Height (without
cable clamp
plates)
Height (with
cable clamp
plates)
Width
Depth
(without options
installed on
JCU)
Depth
(with options
installed on
JCU)
Weight
mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) kg (lbs)
A 364 (14.33) 474 (18.66) 90 (3.54) 146 (5.75) 169 (6.65) 2.8 (6.2)
B 380 (14.96) 476 (18.74) 100 (3.94) 223 (8.78) 246 (9.69) 4.8 (10.6)
C 467 (18.39) 558 (21.97) 165 (6.50) 235 (9.25) 248 (9.76) 10 (22)
D 467 (18.39) 558 (21.97) 220 (8.66) 235 (9.25) 248 (9.76) 17 (37.5)
Drive type
ACSM1-04xx…
Power loss
W
Air flow
(ACSM1-04A…)
m
3
/h
Air flow
(ACSM1-04C…)
m
3
/h
Noise level
dBA
-02A5-4 100 24 N/A 47
-03A0-4 106 24 N/A 47
-04A0-4 126 24 N/A 47
-05A0-4 148 24 N/A 47
-07A0-4 172 24 N/A 47
-09A5-4 212 48 N/A 39
-012A-4 250 48 N/A 39
-016A-4 318 48 N/A 39
-024A-4 375 142 24 63
-031A-4 485 142 24 63
-040A-4 541 200 24 71
-046A-4 646 200 24 71
-060A-4 840 290 24 70
-073A-4 1020 290 24 70
-090A-4 1200 290 24 70