Advant Controller 450 Product Guide
3BSE 015 953R201 Rev B 8-30
8 input channels, resolution 12 bits, single-
end., 0 to+10V or 0 to+20mA, shunt 250Ω 0.05%
8 outp. chann., resol. 12 bits, 0 to +20 mA or
0 to +10 V (over shunt 500 Ω 0.1% on
DSTA 001A or DSTA 001B)
DSAX 110
DSTA 001A
DSTK 230L5
or
DSAX 110A
DSTA 001B
DSTK 230L5
3BSE019940R1
With redundancy: 8 input channels, resolution
12 bits, single-ended, 0 to +10 V or 0 to +20 mA,
shunt 250 Ω 0.05%
8 outp. channels, resol. 12 bits, 0 to +20mA or
0 to+10V (over shunt 500Ω 0.1% on DSTA 001A
or DSTA 001B)
2xDSAX 110
DSTA 001A
DSTK 230L5
DSTK 223L3
or
2xDSAX 110A
DSTA 001B
DSTK 230L5
DSTK 223L3
3BSE019941R1
Table 8-53. S100 I/O for Intrinsic Safety Isolator support (without connection units)
Description Consists of Article No.
16 channels, resolution 12 bit, differential
0 to ±10 V or 0 to ±20 mA, shunt 250 Ω 0.1%
CMV 100 V, CMRR > 100 dB (50 Hz)
Cable length: 10m (32.8 ft.)
16 channels, resolution 12 bit, differential
0 to ±10 V or 0 to ±20 mA, shunt 250 Ω 0.1%
CMV 50 V, CMRR > 100 dB (50 Hz)
Cable length: 10m (32.8 ft.)
DSAI 130
DSTK 225SL10
or
DSAI 130A
DSTK 225SL10
3BSE019942R1
16 channels, resolution 12 bit, differential
0 to ±10 V or 0 to ±20 mA, shunt 250 Ω 0.1%
CMV 100 V, CMRR > 100 dB (50 Hz)
Cable length: 15m (49.2 ft.)
16 channels, resolution 12 bit, differential
0 to ±10 V or 0 to ±20 mA, shunt 250 Ω 0.1%
CMV 50 V, CMRR > 100 dB (50 Hz)
Cable length: 15m (49.2 ft.)
DSAI 130
DSTK 225SL15
or
DSAI 130A
DSTK 225SL15
3BSE019944R1
Table 8-52. S100 I/O boards for HART Protocol Interface (Continued)
Description Consists of Article No.