B68 Installation Guide
Table 14 DNP3 tables
Binary input points list
Point
Index
Name Event class
Assigned (1, 2, 3
or none)
Name for state
when value is 0
Name for state
when value is 1
Description
0 Sys-Ready none OFF ON System Ready
1 Sys-Warn none OFF ON System warning
2 Sys-Crit none OFF ON System critical
3 Hyd-Lev-Warn none OFF ON Hydrogen level warning
4 Hyd-Lev-Crit none OFF ON Hydrogen level critical
5 Hyd-RoC-Warn none OFF ON Hydrogen RoC warning
6 Hyd-RoC-Crit none OFF ON Hydrogen RoC warning
7 Moi-Lev-Warn none OFF ON Moisture level warning
8 Moi-Lev-Crit none OFF ON Moisture level critical
9 Moi-RoC-Warn none OFF ON Moisture RoC warning
10 Moi-RoC-Crit none OFF ON Moisture RoC warning
Generic Modbus Sensor 1
11 <name>-Lev-Warn none OFF ON Sensor level warning
12 <name>-Lev-Crit none OFF ON Sensor level warning
13 <name>-RoC-Warn none OFF ON Sensor level warning
14 <name>-RoC-Crit none OFF ON Sensor level warning
Generic Modbus Sensor 2
15 <name>-Lev-Warn none OFF ON Sensor level warning
16 <name>-Lev-Crit none OFF ON Sensor level warning
17 <name>-RoC-Warn none OFF ON Sensor level warning
18 <name>-RoC-Crit none OFF ON Sensor level warning
Generic Modbus Sensor 3
19-22 Generic Modbus Sensor 3 binary input points block
Generic Modbus Sensor 4
23-26 Generic Modbus Sensor 4 binary input points block
Generic Modbus Sensor 5
27-30 Generic Modbus Sensor 5 binary input points block
Analog input points list
Point
Index
Name Event class
Assigned
(1, 2, 3 or
none)
Min
int/flt
Max
int/flt
Multiplier Offset Units Resolution Description
0 Hydrogen none / / 1 0 PPM Hydrogen (ppm)
1 Hyd_RoC_Day none / / 1 0 PPM/
Day
Hydrogen RoC
(ppm/day)