CoreSense Hub option B69
Analog input points list
Point
Index
Name Event class
Assigned
(1, 2, 3 or
none)
Min
int/flt
Max
int/flt
Multiplier Offset Units Resolution Description
2 Hyd_RoC_Week none / / 1 0 PPM/
Week
RESERVED –
Hydrogen RoC
(ppm/week)
3 Hyd_RoC_
Month
none / / 1 0 PPM/
Month
RESERVED –
Hydrogen RoC
(ppm/month)
4 Oil_Temp none / / 1 0 Celsius Oil Temperature
(moisture)
5 Moi_Aw none / / 0.01 0 Moisture (aw)
6 Moisture none / / 1 0 PPM Moisture (ppm)
7 Moi_Day none / / 1 0 PPM/
Day
Moisture RoC
(ppm/day)
8 Moi_Week none / / 1 0 PPM/
Week
RESERVED –
Moisture RoC
(ppm/week)
9 Moi_Month none / / 1 0 PPM/
Month
RESERVED –
Moisture RoC
(ppm/month)
10 Input_1 none / / 0.01 0 mA 4–20 mA Input 1
11 Input_2 none / / 0.01 0 mA 4–20 mA Input 2
12 Input_3 none / / 0.01 0 mA 4–20 mA Input 3
Calculated Values
13 Aging none / / 1 0 Days Aging
14 Hotspot none / / 1 0 Celcius Hotspot
15 Load Ratio none / / 1 0 % Load Ratio
16 Loss of Life none / / 1 0 Minutes Loss of Life
17 Overload
Capacity
none / / 1 0 % Overload Capacity
5 minutes
18 Overload
Capacity
none / / 1 0 % Overload Capacity
15 minutes
19 Overload
Capacity
none / / 1 0 % Overload Capacity
30 minutes
20 Overload
Capacity
none / / 1 0 % Overload Capacity
60 minutes
21 Overload
Capacity
none / / 1 0 % Overload Capacity
120 minutes
Generic Modbus Sensor 1
22 Sensor_value none / / 1 0 Sensor value
23 Sensor_RoC_
Day
none / / 1 0 Sensor RoC
24 RESERVED none / / 1 0 RESERVED
25 RESERVED none / / 1 0 RESERVED