B70 Installation Guide
Analog input points list
Point
Index
Name Event class
Assigned
(1, 2, 3 or
none)
Min
int/flt
Max
int/flt
Multiplier Offset Units Resolution Description
26 RESERVED none / / 1 0 RESERVED
27 RESERVED none / / 1 0 RESERVED
28 RESERVED none / / 1 0 RESERVED
29 RESERVED none / / 1 0 RESERVED
30 RESERVED none / / 1 0 RESERVED
31 RESERVED none / / 1 0 RESERVED
Generic Modbus Sensor 2
23-32 Generic Modbus Sensor 2 analog input points block
Generic Modbus Sensor 3
33-42 Generic Modbus Sensor 3 analog input points block
Table 15 IEC-60870-5-104 table
Point
Index
Type Name Scale Min
(if applicable)
Scale Max
(if applicable)
Units
0-99 Reserved for future use
100 9
Hydrogen
0 5000
ppm101 11 0 5000
102 13
103 1 Hydrogen Alarm
104 1 Hydrogen Warning
105 9
Hydrogen Rate of change (daily)
-5000 5000
ppm/day106 11 -5000 5000
107 13
108 1 Hydrogen Rate of change (daily) Alarm
109 1 Hydrogen Rate of change (daily) Warning
110 9
RESERVED - Hydrogen Rate of change (weekly)
-5000 5000
ppm/week111 11 -5000 5000
112 13
113 1 RESERVED - Hydrogen Rate of change (weekly) Alarm
114 1 RESERVED - Hydrogen Rate of change (weekly) Warning
115 9
RESERVED - Hydrogen Rate of change (monthly)
-5000 5000
ppm/month116 11 -5000 5000
117 13
118 1 RESERVED - Hydrogen Rate of change (monthly) Alarm
119 1 RESERVED - Hydrogen Rate of change (monthly) Warning