ACH550-UH User’s Manual 105
Start-Up
3405 OUTPUT1 DSP UNIT -128…127 1 4
Selects the units used with the first display parameter.
• Enter positive values in parameter 3405 for a numeric display.
• Enter negative values in parameter 3405 for a bar-graph display.
3406 OUTPUT1 MIN Depends on selection - 0.0%
Sets the minimum value displayed for the first display parameter.
3407 OUTPUT1 MAX Depends on selection - 1000.0%
Sets the maximum value displayed for the first display parameter.
3408 SIGNAL 2 PARAM 100…199 1 104
Selects the second parameter (by number) displayed on the control panel. See parameter 3401.
3409 SIGNAL 2 MIN Depends on selection - 4.3 A
Defines the minimum expected value for the second display parameter. See parameter 3402.
3410 SIGNAL 2 MAX Depends on selection - 9.2 A
Defines the maximum expected value for the second display parameter. See parameter 3403.
3411 OUTPUT 2 DSP FORM 0…8 1 5
Defines the decimal point location for the second display parameter. See parameter 3404.
3412 OUTPUT 2 DSP UNIT -128…127 1 1
Selects the units used with the second display parameter. See parameter 3405.
3413 OUTPUT 2 MIN Depends on selection - 0.0 A
Sets the minimum value displayed for the second display parameter. See parameter 3406.
3414 OUTPUT 2 MAX Depends on selection - 9.2 A
Sets the maximum value displayed for the second display parameter. See parameter 3407.
3415 SIGNAL 3 PARAM 100…199 1 120
Selects the third parameter (by number) displayed on the control panel. See parameter 3401.
3416 SIGNAL 3 MIN Depends on selection 0.0%
Defines the minimum expected value for the third display parameter. See parameter 3402.
3417 SIGNAL 3 MAX Depends on selection 100.0%
Defines the maximum expected value for the third display parameter. See parameter 3403.
3418 OUTPUT 3 DSP FORM 0…8 1 5
Defines the decimal point location for the third display parameter. See parameter 3404.
3419 OUTPUT 3 DSP UNIT -128…127 1 11
Selects the units used with the third display parameter. See parameter 3405.
3420 OUTPUT 3 MIN Depends on selection 0.0 mA
Sets the minimum value displayed for the third display parameter. See parameter 3406.
Group 34: Panel Display Process Variables
Code Description Range Resolution Default S
0 = NOT SEL 8 = kh 16 = °F 24 = GPM 32 = kHz 40 = m
3
/m 48 = gal/m 56 = FPS
1 = A 9 = °C 17 = hp 25 = PSI 33 = Ohm 41 = kg/s 49 = gal/h 57 = ft/s
2 = V 10 = lb ft 18 = MWh 26 = CFM 34 = ppm 42 = kg/m 50 = ft
3
/s 58 = inH
2
O
3 = Hz 11 = mA 19 = m/s 27 = ft 35 = pps 43 = kg/h 51 = ft
3
/m 59 = in wg
4 = % 12 = mV 20 = m
3
/h 28 = MGD 36 = l/s 44 = mbar 52 = ft
3
/h 60 = ft wg
5 = s 13 = kW 21 = dm
3
/s 29 = inHg 37 = l/min 45 = Pa 53 = lb/s 61 = lbsi
6 = h 14 = W 22 = bar 30 = FPM 38 = l/h 46 = GPS 54 = lb/m 62 = ms
7 = rpm 15 = kWh 23 = kPa 31 = kb/s 39 = m
3
/s 47 = gal/s 55 = lb/h 63 = Mrev
117 = %ref 119 = %dev 121 = % SP 123 = Iout 125 = Fout 127 = Vdc
118 = %act 120 = % LD 122 = %FBK 124 = Vout 126 = Tout