Serial Communication – FBA
The serial communication channel is defined as the source for controlling
commands from EXT1 (set using parameters 1001 EXT1 COMMANDS and 1102
EXT1/EXT2 SEL).
The external plug-in fieldbus adapter is activated:
Parameter 9802 COMM PROT SEL = 4 (EXT FBA).
The external plug-in fieldbus adapter is configured to use the drive profile
mode or drive profile objects.
The content of the CONTROL WORD depends on the protocol/profile used. See the
users manual provided with the FBA module and/or the "ABB Drives Profile
Technical Data".
Status Word
The STATUS WORD is a 16-bit word containing status information, sent by the drive to
the fieldbus controller. The content of the
STATUS WORD depends on the protocol/
profile used. See the users manual provided with the FBA module and/or the "ABB
Drives Profile Technical Data" section.
Reference
The contents of each REFERENCE word:
Can be used, as speed or frequency reference.
Is a 16-bit word comprised of a sign bit and a 15-bit integer.
Negative references (indicating reversed rotation direction) are indicated by the
two’s complement of the corresponding positive reference value.
The use of a second reference (REF2) is supported only when a protocol is
configured for the ABB Drives profile.
Reference scaling is fieldbus type specific. See the user’s manual provided with the
FBA module and/or the following sections as appropriate:
"ABB Drives Profile Technical Data"
"Generic Profile Technical Data"
Actual Values
Actual Values are 16-bit words containing information on selected operations of the
drive. Drive Actual Values (for example, group 01 parameters) can be mapped to
Input Words using group 51 parameters (protocol-dependent, but typically
parameters 5104…5126).
Planning
Network planning should address the following questions:
What types and quantities of devices must be connected to the network?
What control information must be sent down to the drives?
What feedback information must be sent from the drives to the controlling
system?

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB DriveIT ACH550-UH and is the answer not in the manual?

ABB DriveIT ACH550-UH Specifications

General IconGeneral
CategoryDC Drives
ModelACH550-UH
Input Voltage380 ... 480 V AC
CommunicationEthernet, PROFIBUS
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overtemperature, Short circuit
Control MethodSensorless vector control

Related product manuals